Kitchen Hood / Range Hood Calculator
Enter kitchen size, cooktop width, and how you cook to estimate the airflow your extractor hood should move. The tool compares room air changes, cooktop width, and gas BTU — then takes the strongest requirement.
Calculate
Values convert when you switch metric ↔ imperial.
Result
The formula
Three planning drivers set the target airflow: kitchen volume × air changes per hour, cooktop width × a wall/island rate, and (for gas) total burner BTU ÷ 100. The recommended CFM is the largest of those values (minimum 100 CFM), rounded up to a practical stock size. Metric results show cubic metres per hour (m³/h ≈ CFM × 1.7).
Worked example
- Kitchen 4 m × 3 m × 2.7 m → volume ≈ 32.4 m³ ≈ 1,144 ft³
- Mixed cooking at 15 ACH → Q_room = 1,144 × 15 ÷ 60 ≈ 286 CFM
- 60 cm wall cooktop → 1.97 ft × 100 ≈ 197 CFM; electric (no BTU driver)
- max(286, 197, 100) → round to 300 CFM ≈ 510 m³/h
Result: ≈ 300 CFM (510 m³/h) — room air-change rule governs
How kitchen hood airflow is sized
Home range-hood charts combine a room-volume air-change screen with cooktop capture rules. This calculator follows that transparent approach and states where it stops short of a full kitchen ventilation design.
Room volume and air changes
Kitchen volume is length × width × ceiling height. An air-changes-per-hour (ACH) rate estimates how often the room air should turn over while cooking: about 10 ACH for light baking, 15 for everyday mixed cooking, and 20 for frequent frying or grilling. Divide volume (ft³) × ACH by 60 to get CFM.
Cooktop width and hood mount
Capture rules size the hood to the cooktop. A common planning rate is 100 CFM per linear foot of cooktop for a wall-mounted hood and 150 CFM per foot for an island hood (harder capture from all sides). Enter the cooktop width, not the hood canopy width.
Gas burner output
Gas ranges add combustion products and more heat. A widely used screen is total burner BTU/h ÷ 100 = CFM. Sum all burners (and griddle if listed). Electric and induction skip this driver.
What this calculator does not model
It does not size duct equivalent length, makeup-air systems, noise (sones), grease filters, or commercial Type I hoods. Local codes may require makeup air above roughly 400 CFM. Confirm with the hood maker’s installation guide and a qualified installer.
Interesting facts
CFM and m³/h measure the same airflow
Cubic feet per minute (CFM) is common in North America; cubic metres per hour (m³/h) dominates European labels. Multiply CFM by about 1.7 for m³/h (divide m³/h by 1.7 for CFM).
Island hoods usually need more airflow
Without a back wall to help contain the plume, island mounts often use a higher CFM-per-foot rule than wall hoods of the same cooktop width.
Oversized hoods are louder and can starve the house of air
Very high CFM without makeup air can pull combustion appliances back-draft. Quieter cooking often needs good capture design more than raw maximum speed.
Duct diameter matters as much as fan rating
A strong fan on undersized flexible duct loses real airflow to friction. Smooth rigid duct near the manufacturer’s recommended diameter keeps the rated CFM closer to reality.
Recirculating hoods clean grease but do not remove moisture
Ductless charcoal filters catch odours and grease particles; steam and heat still stay in the kitchen. Ducted exhaust is preferred when outdoor venting is allowed.
Frequently asked questions
Compare room volume × ACH ÷ 60, cooktop width × 100–150 CFM/ft, and (for gas) BTU ÷ 100. Buy at least the largest of those — often 200–600 CFM for home kitchens.
Multiply CFM by 1.699 (about 1.7). Example: 300 CFM × 1.7 ≈ 510 m³/h. European product labels usually list m³/h.
A 60 cm (≈24 in) wall cooktop is about 2 linear feet → roughly 200 CFM from the width rule. If the kitchen is large or you fry often, the room ACH number may be higher — use the larger result.
Often yes. Add up burner BTU and divide by 100 for a CFM screen, then compare with width and room rules. Choose the maximum.
Island hoods typically use a higher per-foot rate (about 150 CFM/ft vs 100 CFM/ft for wall) because cooking plumes are harder to capture in the open.
Many residential installs use about 6–7 in (150–180 mm) for mid-range fans and larger diameters as CFM rises. Follow the hood’s installation sheet — undersized duct cuts real airflow.
Some codes require makeup air for high-CFM exhaust (commonly around 400 CFM and above). Check local rules; this calculator only flags the planning threshold.
No. Commercial Type I/II hoods follow different codes (grease duct, fire suppression, exhaust rates per linear foot of cooking equipment). Use a commercial kitchen designer.
References
- Range hoods Consumer overview of ducted vs recirculating range hoods and efficient use.
- Ventilation and Acceptable Indoor Air Quality in Residential Buildings (ASHRAE 62.2) Residential ventilation framework; local codes may adopt related makeup-air rules for large kitchen exhaust.
- Home Ventilating Institute Industry certification context for residential ventilating products including range hoods.